Interactive Inverter Interconnections

Primary tabs

Identifying the Optimal Point of Connection
  • Interactive Inverter Interconnections
    Interactive Inverter Interconnections
  • No service upgrade required
    Green Mountain Power’s customers in Vermont can purchase ConnectDER meter socket adapters directly from the utility. Since the product allows for a supply-side connection, it can both eliminate...
  • Interactive Inverter Interconnections
  • No service upgrade required

The 2014 and 2017 editions of the National Electrical Code provide solar companies with more interconnection options than previous Code editions did. In this article, I offer an overview of the Code requirements and allowances for interconnecting parallel power production sources, such as PV or energy storage systems, to premises wiring supplied by a utility or other primary on-site electric power sources. My goal is to help solar company personnel identify the most appropriate point of connection (POC), which is specific to both the system and the site.

To cover the maximum number of interconnection scenarios in as much detail as possible, I have chosen to focus specifically on distributed generation applications, where parallel power production sources interconnect at utilization voltage levels in properties with on-site loads. I assume that readers have a working knowledge of and access to the NEC, which contains many important definitions and references. In the interest of brevity, I italicize on first use those terms that the NEC defines; if you are unfamiliar with any italicized terms in this article, especially those in Figure 1, please refer to Article 100, “Definitions,” or to the NEC index. I provide Code references in square brackets throughout the article, indicating the 2014 or 2017 revision cycle where relevant.

POC Options

NEC Article 705 details the basic safety requirements for interconnected electric power production sources. Though distributed PV systems are a common parallel power production source, other sources include on-site generators, fuel cells, wind electric systems and some energy storage systems. Regardless of the power source, qualified persons must install these systems [2014-705.6; 2017-705.8] using approved equipment, such as listed interactive inverters certified to UL 1741 [2014-705.4; 2017-705.6].

The first step when planning a safe interconnection is to document relevant PV system equipment ratings. The essential data for Code compliance include utility-interactive inverter output circuit ratings [690.8(A)(3), 705.60(A)(2)] and the associated overcurrent protection device (OCPD) ratings [690.9(B), 705.60(B)]. Where multiple inverters interconnect to a single POC, it is useful to record individual inverter output circuit currents as well as the sum of these currents wherever you combine inverter outputs.

The next step is to assess the configuration and condition of the existing premises wiring, paying special attention to any equipment or locations that provide potential interconnection opportunities. As shown in Figure 2, the Code allows for two basic types of interconnections: supply-side connections [705.12(A)] and load-side connections [2014-705.12(C); 2017-705.12(B)]. Note that the delineation point between supply- or load-side connections is the disconnecting means for the utility-supplied service; this is an important distinction, as feeders rather than services supply some buildings or structures.

As illustrated in Figure 2, multiple potential interconnection opportunities exist on both the load side and the supply side of the service disconnecting means. Generally speaking, cost and complexity increase as the POC moves from left to right. I have generally organized the following scenarios accordingly, from the most common and least complex options to those that are less common and more complex. In most cases, I provide a formula that you can use to evaluate the Code compliance of different interconnection methods using existing equipment. You can easily adapt these formulas to evaluate potential equipment modifications or upgrades, while that is beyond the scope of this article.

Though I focus here on a few key metrics—most notably, supply overcurrent device ratings, panel busbar ratings and feeder conductor sizes—a thorough site survey is a prerequisite for identifying the optimal POC. Ideally, this survey identifies the locations and ratings of the utility transformer, revenue meter, service entrance conductors, main service panel, service disconnecting means, grounding electrode, subpanels, supply breaker ratings, on-site power production sources and even load breaker ratings. In addition to photographing and taking notes on the general as-built conditions, be sure to take pictures of any electrical equipment labels, as these data will invariably prove essential later.

Note that often a manufacturer-applied label on the panelboard identifies the busbar or mains rating for existing equipment. In some cases, however, you may need to find the original equipment documentation to determine this value. If you are unable to document a busbar rating conclusively, the generally accepted practice is to use the rating of the associated OCPD.